Home > Industrial Products > FP0R, Panasonic, Programmable Controllers
FP0R, Panasonic, Programmable Controllers
FP0R, Panasonic, Programmable Controllers
SKU: PROGRAMMABLE-CONTROLLERS-FP0R
Regular price
$94.00
Regular price
Sale price
$94.00
Unit price
/
per
Performance specifications (FP0R Control units)
Product type of FP0R control unit | C10 (Relay output type only) |
C14 (Relay output type only) |
C16 (Transistor output type only) |
||
---|---|---|---|---|---|
Programming method / Control method | Relay symbol / Cyclic operation | ||||
Number of I/O points |
No expansion (Control unit only) |
10 points [Input: 6, Relay output: 4] |
14 points [Input: 8, Relay output: 6] |
16 points [Input: 8, Transistor output: 8] |
|
With expansion 1 Same type of control and expansion units (Note) |
Max. 58 points | Max. 62 points | Max. 112 points | ||
With expansion 2 Mix type of relay and transistor units (Note) |
Max. 106 points | Max. 110 points | Max. 112 points | ||
Program memory | EEPROM (no backup battery required) | ||||
Program capacity | 16 k steps | ||||
Number of instructions |
Basic | 110 approx. | |||
High-level | 210 approx. | ||||
Operation speed | Up to 3,000 steps | Basic instructions: 0.08 μs min. Timer instructions: 2.2 μs min. High-level instructions: 0.32 μs (MV instruction) Min. |
|||
3,001st and later steps | Basic instructions: 0.58 μs min. Timer instructions: 3.66 μs min. High-level instructions: 1.62 μs (MV instruction) Min. |
||||
Operation memory |
Relay | Internal relay (R) |
4,096 points | ||
Timer / Counter (T / C) |
1,024 points | ||||
Memory area | Data register (DT) | 12,315 words | |||
Index register (IX, IY) | 14 words (IO to ID) | ||||
Master control relay points (MCR) | 256 words | ||||
Number of labels (JMP and LOOP) | 256 labels | ||||
Differential points | Equivalent to the program capacity | ||||
Number of step ladder | 1,000 stages | ||||
Number of subroutines | 500 subroutines | ||||
Special functions |
High speed counter (HSC) | Single-phase 6 points (C10: Single-phase 4 points) (50 kHz max. each) or 2-phase 3 points (C10: 2-phase 2 points) (15 kHz max. each) (Note) | |||
Pulse output | Not available | 4 points (50 kHz max. each) 2 channels can be controlled individually.(Note) | |||
PWM output | Not available | 4 points (6 Hz to 4.8 kHz) | |||
Pulse catch input / interrupt input |
Total 8 points (with high speed counter) | ||||
Interrupt program | Input: 8 programs (6 programs for C10 only) / Periodic: 1 program / High speed counter match, Pulse output match: 4 programs | ||||
Periodical interrupt | In units of 0.5 ms: 0.5 ms to 1.5 sec. / In units of 10 ms: 10 ms to 30 sec. | ||||
Constant scan | In units of 0.5 ms: 0.5 ms to 600 ms | ||||
RS-232C port | One RS-232C port is mounted on each of C10CRS, C10CRM, C14CRS, C14CRM, C16CT, C16CP, C32CT, C32CP, T32CT, T32CP, F32CT and F32CP type (3P terminal block) Transmission speed (Baud rate): 2,400 to 115,200 bits/sec, Transmission distance: 15 m 9.843 ft. Communication method: half duplex |
||||
RS-485 port | One RS-485 port is mounted on each of C10MRS, C14MRS, C16MT, C16MP, C32MT, C32MP, T32MT, T32MP, F32MT and F32MP type(3P terminal block) Transmission speed (Baud rate): 115.2 kbps (It is possible to change to 19.2 kbps by the setting.), Transmission distance: 1,200 m 3,937 ft, Communication method: half duplex |
||||
Maintenance | Memory backup |
Program and system register |
Stored program and system register in EEPROM | ||
Operation memory |
Stored fixed area in EEPROM Counter: 16 points Internal relay: 128 points Data register: 315 words |
||||
Self-diagnostic function |
Watchdog timer (690 ms approx.), Program syntax check | ||||
Real-time clock function |
Not available | ||||
Other functions | Rewriting in RUN mode (Simultaneous rewriting capacity: 512 steps), Download in RUN mode (All programs), Password function (4-digit, 8-digit), Read protection setting |
Product type of FP0R control unit | C32 (Transistor output type only) |
T32 (Transistor output type only) |
F32 (Transistor output type only) |
||
---|---|---|---|---|---|
Programming method / Control method | Relay symbol / Cyclic operation | ||||
Number of I/O points |
No expansion (Control unit only) |
32 points [Input: 16, Transistor output: 16] |
32 points [Input: 16, Transistor output: 16] |
||
With expansion 1 Same type of control and expansion units (Note) |
Max. 128 points | Max. 128 points | |||
With expansion 2 Mix type of relay and transistor units (Note) |
Max. 128 points | Max. 128 points | |||
Program memory | EEPROM (no backup battery required) | ||||
Program capacity | 32 k steps | ||||
Number of instructions |
Basic | 110 approx. | |||
High-level | 210 approx. | ||||
Operation speed | Up to 3,000 steps | Basic instructions: 0.08 μs Min. Timer instructions: 2.2 μs Min. High-level instructions: 0.32 μs (MV instruction) Min. |
|||
3,001st and later steps | Basic instructions: 0.58 μs Min. Timer instructions: 3.66 μs Min. High-level instructions: 1.62 μs (MV instruction) Min. |
||||
Operation memory |
Relay | Internal relay (R) |
4,096 points | ||
Timer / Counter (T / C) |
1,024 points | ||||
Memory area | Data register (DT) | 32,765 words | |||
Index register (IX, IY) | 14 words (IO to ID) | ||||
Master control relay points (MCR) | 256 words | ||||
Number of labels (JMP and LOOP) | 256 labels | ||||
Differential points | Equivalent to the program capacity | ||||
Number of step ladder | 1,000 stages | ||||
Number of subroutines | 500 subroutines | ||||
Special functions |
High speed counter (HSC) | Single-phase 6 points (50 kHz max. each) or 2-phase 3 points (15 kHz max. each) (Note) | |||
Pulse output | 4 points (50 kHz max. each) 2 channels can be controlled individually.(Note) | ||||
PWM output | 4 points (6 Hz to 4.8 kHz) | ||||
Pulse catch input / interrupt input |
Total 8 points (with high speed counter) | ||||
Interrupt program | Input: 8 programs (6 programs for C10 only) / Periodic: 1 program / High speed counter match, Pulse output match: 4 programs | ||||
Periodical interrupt | In units of 0.5 ms: 0.5 ms to 1.5 sec. / In units of 10 ms: 10 ms to 30 sec. | ||||
Constant scan | In units of 0.5 ms: 0.5 ms to 600 ms | ||||
RS-232C port | One RS-232C port is mounted on each of C10CRS, C10CRM, C14CRS, C14CRM, C16CT, C16CP, C32CT, C32CP, T32CT, T32CP, F32CT and F32CP type (3P terminal block) Transmission speed (Baud rate): 2,400 to 115,200 bits/sec, Transmission distance: 15 m 9.843 ft. Communication method: half duplex |
||||
RS-485 port | One RS-485 port is mounted on each of C10MRS, C14MRS, C16MT, C16MP, C32MT, C32MP, T32MT, T32MP, F32MT and F32MP type(3P terminal block) Transmission speed (Baud rate): 115.2 kbps (It is possible to change to 19.2 kbps by the setting.), Transmission distance: 1,200 m 3,937 ft, Communication method: half duplex |
||||
Maintenance | Memory backup |
Program and system register |
Stored program and system register in EEPROM | ||
Operation memory |
Stored fixed area in EEPROM Counter: 16 points Internal relay: 128 points Data register: 315 words |
Backup of the entire area by FeRAM (without the need for a battery) |
|||
Backup of the entire area by a built-in secondary battery | |||||
Self-diagnostic function |
Watchdog timer (690 ms approx.), Program syntax check | ||||
Real-time clock function |
Not available | Available | Not available | ||
Other functions | Rewriting in RUN mode (Simultaneous rewriting capacity: 512 steps), Download in RUN mode (All programs), Password function (4-digit, 8-digit), Read protection setting |
Weight: C10: 100g, C14: 105g, C16: 85g, C32: 115g, T32: 115g, F32: 120g